The DGC-06:Digital Multi-Gas Controller System is designed to monitor and alert for toxic and combustible gases, vapors, and refrigerants across various gas measurements.
This controller system monitors and controls up to 128 gas types, 96 digital sensors, and 32 analog sensor options. It includes four freely adjustable alarm thresholds per connected sensor, meeting key safety code requirements such as EN50545-1 for CO monitoring, EN 378, and VBG 20 for NH3 monitoring.
Note: The DGC-06 operates exclusively with the Fixed Multi-Gas Detector Series or Combustible Fixed Gas Detectors.
Features
Modular, user-friendly design suited for large facilities
128 gas sensor capacities
Four adjustable alarm thresholds per sensor
Five menu languages and adjustable settings
Configurable relays for various alarms
Alarm activation by rising or falling gas concentrations
PCE06 Software connector at the controller module
Flexible configuration with programmable parameters and set points
Warning buzzer/LED alarm with fault and operation options
Broad BMS compatibility
SIL2 Level Compliance
Specifications
Measurement Range: Dependent upon gas sensors selected
Housing Type C/E: Plastic Housing with View Cover
Gas Type: Dependent upon gas sensors selected
Installation: Wall Mounted
Ingress Protection: IP65
Knockouts for Cable Entry: Standard 6× M20/25
Storage Temp Range: 32 °F to 104 °F (0 °C to +40 °C)
Temperature Range: 23 °F to 104 °F (-5 °C to +40 °C)
Power Supply: 90/230 V AC, 50/60 Hz; 24 VDC ± 20 %
Humidity Range: 15-95 % RH non-condensing
Tension for external analog transmitter: 24 VDC ±20 %, max130 mA - per sensor
Power Consumption: Min. 30 W, 0.15 A, max. ca. 160 W, 0.7 A, depending on the type
Analog Input (4 to max. 32): 4–20 mA, overload and short-circuit proof, input resistance 130 µ
Analog output (max 16) configurable for each input:
4–20 mA = measuring range
Proportional, overload, and short-circuit proof, charge ≤ 500 µ
20–21.2 mA = over range
3.0–<4 mA = under range
2.0 mA = fault
Relay (max. 32): 250 VAC, 5 A; 30 V DC, 2 A, potential-free, change-over (SPDT)
Fault relay (1): 250 VAC, 5 A; 30 VDC, 2 A, potential-free, normally open contact (SPST)
Transceiver: RS485 / 19200 Baud
Dimensions: W × H × D - 11.7 × 10.2 × 5.5 in. | (298 × 260 × 140 mm)
Weight: Min. 4.4 Ib. (2.7 kg), max. 28.7 Ibs. (13 kg) depending on type
Weight: 1.32 lbs. (0.6 kg)
Menu Language (selectable): German, English, French, or Italian
Regulations
EMC Directive 2014/30/EU
ANSI/UL 61010-1
Low Voltage Directive 2014/35/EU
EN 61010-1:2010
EN 50271
CAN/CSA-C22.2 No. 61010-1
EN 50545-1
Warranty
1 year
Accessories
Options
MSC-2 | Multi-Gas Fixed Gas Detector
SC2-E1130-B-P-00 | NO2 Digital Sensor for MSC2
SC2-E1110-A-P-00 | CO Digital Sensor for MSC2
SC2-E1195-A2-P-00 | O2 Digital Sensor for MSC2
SC2-E1194-A-P-00 | H2 Digital Sensor for MSC2
SC2-I464-B-P-00 | CO2 Digital Sensor for MSC2
For over 25 years, Borealis has been a leading provider of polyolefins, base chemicals, and ferti……...
Formed in 1984 to focus on the fire alarm systems market, today System Sensor is one of the large……...
The NCR-86 radar level sensor is highly adaptable and designed to continuously measure solids of ……...
We have been developing and manufacturing precision sensors for position and distance measurement……...
Oven Industries has specialized in the design and manufacture of custom electronic control system……...
Magnetic Component Engineering, Inc. is the Supplier of neodymium magnets, samarium cobalt magnet……...
The panel measuring table supplies fast information on the etching distribution after differential etching processes or on the thickness of copper plating. The measurements are carried out fully au……
Oakton Temp-300 Dual-Input Thermocouple Datalogging Thermometer logs up to 2000 sets of readings in real time with date and time stamp. USB output lets you transfer data to your computer. Automatic……
Monnit Corporation was established to capitalize on the emerging trend of connecting to, monitoring and controlling machines and other “things” in our environment. Their backgrounds in ……